CL-920 Custom RJ11 RS485 Port Programming

    


After the software in controlling client is completed, please proceed with programming the same way as programming the remote control:


1. Press and Hold the “Programming button” at the bottom of the motor for about 5 seconds until the LED light is on.
2. Send the “OPEN” command from the controlling device to the motor. ( “OPEN” command 129, 1, 2, 3, 1, 2, 166)
3. If the setting is done correctly, the LED light will flash and then go off.
4. Now the motor and controlling device are paired and communicating.

 



BYTE 1

Bit 7    

Bit 6    

Bit 5    

Bit 4    

Bit 3    

Bit 2    

Bit 1    

Bit 0    

Bit7=1 (corresponds to: the controlling device controls the motor)
Bit7=0 (corresponds to: the motor feedback information to the controlling device)
Bit0=1 (correcponds to: this is curtain motor)
=0X81=129


BYTE 2
BYTE 3
BYTE 4
BYTE 5
Are all address for the device=


BYTE 6 - Controlling Byte

Possibe values are:
2=OPEN (or Programming)
3=STOP
4=CLOSE
6=ENQUIRING


BYTE 7 - Verification Byte


 

RS-485 Communication Protocol

The master controlling device sends one package of data to the curtain motor, the curtain motor will respond with data back.
The curtain motor does not send data to the master controlling device on its own initiative.
Baud rate: 9600

The format of RS485 is as follows: 1 bit starting position-“8-bit data” -1 bit stop position.
The definition of Half-dual-way RS485 communication protocol.

1. The package of data which the master controlling device sends to the curtain motor.

Byte1

Byte 2

Byte 3

Byte 4

Byte 5

Byte 6

Byte 7

Device Type    

Address I    

Address II    

Address III    

Device

Channel    

Controlling    

Byte

Verification    

Byte

 

Device Type:

Bit7: Send and Receive symbol:
           1=master device sends to curtain motor
           0=curtain motor responds to master device


Bit6-Bit5:Reserved as blank
Bit4-Bit0:Device type, definition of 1-32 device type as below:
                 1=curtain motor

 

Address I, II, III:
           Master Fixed ID set by factory.

Device Channel:
            1=Channel 1, total 1-255.

Controlling Byte:
             Bit 2=OPEN(ALSO PROGRAMMING)
             Bit 3=STOP
             Bit 4=CLOSE
             Bit 6=ENQUIRING CURRENT STATUS OF CURTAIN MOTOR

Verification Byte:
             Verification Byte=DEVICE TYPE * 1+ ADDRESS I * 2 + ADDRESS II * 3+ ADDRESS III * 4 + DEVICE CHANNEL * 5 + CONTROLLING BIT * 6


 


2. When curtain motor receives the data from master controlling device, and confirms it is used to control the current curtain motor, within 50ms, the curtain motor will clear the bit 7 as 0, and responds it to master controlling device to tell the data is well received.


The responding data format is as below:

Byte1

Byte2

Byte3

Byte4

Byte5

Byte6

Byte7

Device type    

Address I    

Address II    

Address III    

Device

Channel    

Current Status    

of Curtain

Verification Bit    

 

Device Type:

Bit7: Send and Receive symbol:
           1=master device sends to curtain motor
           0=curtain motor responds to master device

Bit6-Bit5:Reserved as blank
Bit4-Bit0:Device type, definition of 1-32 device type as below
                 1=curtain motor

 

Device Channel:
                 1=Channel 1, total 1-255

 

Current Status of Curtain:
              1=curtain fully open
          100=curtain fully closed
         2-99=the current position = length percentage of the total length
          170=curtain motor does not enter the model of electronic counting stop
          187=the motor stopped due to hindrance and bounce back
            50=the curtain is in the center of the total length

 

Verification Byte:

            Verification Byte=DEVICE TYPE * 1+ ADDRESS I * 2 + ADDRESS II * 3+ ADDRESS III * 4 + CHANNEL NUMBER * 5 + CONTROLLING BIT * 6


 


3. When there is not only one curtain motor connecting to one master controlling device, connect All “A” together and all “B” together.


The master controlling device must program each curtain motor one by one, and do not control 2 or more curtain motors in one channel. Otherwise there will be a conflict in RS485 address-finding.

For example, there are 3 curtain motors in one RS485, and the address is 1,2,3, and the channel is 1,2,3 correspondingly. The motor is capable to control the motor 1 by select channel 1, and the data format is[129, 1, 2, 3, 1, 2, 166] decimal system number. Curtain Motor 1 received the data and responds the data format [1, 1, 2, 3,1, 2, 38] decimal system number by RS485 wire to confirm and the curtain will open.


It is possible to find out the position of curtain 1 as follows:
The master controlling device sends [129, 1, 2, 3, 1, 6,190] to enquire the status of the curtain, and in case the curtain is in the center, then the curtain motor responds data [1, 1, 2, 3, 1, 50, 46] decimal system number by RS485 wire.